Load throw-off management
1. Intro
Given the following context:
- Multiple consumers
- Some consumers require constant electrical supply
- Others have a variable need for electrical supply
The load throw-off feature helps manage the electrical supply distribution in that context. Following are some example scenarios to help introduce the feature in more detail.
2. Example scenario 1
A factory operates a staff canteen and provides 10 EV chargers for company fleet cars. Both facilities operate with the same contract, encouraging load limits of 3 x 250A. During service hours, the kitchen consumes up to
150A on L1 100A on L2 and 100A on L3.
A signal is provided when the kitchen is not busy, and consumption falls below 10A.
- The EV charging infrastructure may consume 240A when the kitchen is not busy (=250A – 10A)
- As soon as the kitchen is not used, the control electronics provides a 12V DC signal and the full 3 x 240A may be used by the DLM system.
- When the kitchen is in use, the load of
needs to be thrown off to not exceed the 3 x 250A limit. In that case the DLM may only consumeL 1 L 2 L 3 140A 90A 90A
.L 1 L 2 L 3 100A 150A 150A
2.1. Configuring the Master Charge Controller
-
Apply the following configuration:
Location in Configuration Interface | Parameter | Value | |||||
---|---|---|---|---|---|---|---|
Load Management > Dynamic Load Management | Dynamic Load Management - DLM Master/Slave | DLM Master (With internal DLM-Slave) | |||||
EVSE Sub Distribution (L1/L2/L3)[A] |
| ||||||
External Input 1 Config | Enable Opto 1 in | ||||||
External Input 1 Polarity | Active low | ||||||
External Input 1 Current Offset |
|
- At the bottom of the Configuration Interface, click , then click to apply the changes
2.2. Configuring the Slave Charge Controller
-
Apply the following configuration:
Location in Configuration Interface | Parameter | Value |
---|---|---|
Load Management > Dynamic Load Management | Disconnected Limit [A] | 10 |
- At the bottom of the Configuration Interface, click , then click to apply the changes
3. Example scenario 2
A grid operator uses ripple control to throw-off loads. In this example, one (or multiple) 22kW wall-box must reduce load to 3 x 7A (5kW), when a control signal is low.
3.1. Configuring the Master Charge Controller
-
Apply the following configuration:
Location in Configuration Interface | Set Parameter | to | |||||
---|---|---|---|---|---|---|---|
Load Management > Dynamic Load Management | Dynamic Load Managemen - DLM Master/Slave | DLM Master (With internal DLM-Slave) | |||||
EVSE Sub Distribution Limit (L1/L2/L3)[A] |
| ||||||
External Input 1 Config | Enable Opto 1 in | ||||||
External Input 1 Polarity | Active low | ||||||
External Input 1 Current Offset |
| ||||||
Disconnected Limit [A] | 7 |
- At the bottom of the Configuration Interface, click , then click to apply the changes
3.2. Configuring the Slave Charge Controller
-
Apply the following configuration:
Location in Configuration Interface | Parameter | Value |
---|---|---|
Load Management > Dynamic Load Management | Disconnected Limit [A] | 7 |
- At the bottom of the Configuration Interface, click , then click to apply the changes
4. Limitations of the Load throw-off function
- The load can only be reduced instantly and not gradually over a time interval
- With DLM active, only the current can be reduced, not the power (reduction 32A 🡒 7A, but not 22kW 🡒 5kW)