OCPP status notification error messages
info
Error activation message is the message that is sent when the error occurred. Error resolution message (if any) is sent when the error is corrected. Some errors may be corrected by external events during operation (e.g. temperature is normal again), while some may be resolved after a reset, power cycle or replacement of a faulty part.
OCPP Error code | Error activation message | Error resolution message | Transaction and charging is stopped | Notes | Corrective actions |
---|---|---|---|---|---|
groundFailure | Residual current detected via sensor | Residual current situation resolved | Yes | Internal RCMB device (yellow coil). This detects also DC residual current. | The safety mechanism is reset to its original state every time the cable is unplugged from the chargepoint. Otherwise the error is automatically reset after a delay of 10 seconds if the EV was unplugged. In case the RCMB version is older than or equal to D0469, the delay is 15 minutes. If the problem persists, please check the yellow current transformer (coil) and its connection. |
mode3Error | Vehicle signals error | Vehicle error resolved | No | Mode3 errors. | Disconnect EV and try again. If that doesn’t help, follow EV’s instructions. |
mode3Error | Vehicle diode check failed - tamper detection | Vehicle with diode problem disconnected | Yes | Mode3 errors. | Disconnect EV and try again. If that doesn’t help, follow EV’s instructions. |
overCurrentFailure | MCB of type 2 socket triggered | MCB type 2 reconnected | Yes | MCB needs to be re-armed, requires a maintenance visit. | |
overCurrentFailure | MCB of domestic socket triggered | MCB domestic socket reconnected | Yes | MCB needs to be re-armed, requires a maintenance visit. | |
groundFailure | RCD triggered | RCD reconnected | Yes | External RCD Device. | Up to a certain point this will be corrected automatically. |
groundFailure | RCD may be triggered (OCPP meter power loss) | RCD may be reconnected (OCPP meter recovered) | Yes | External RCD Device. | Up to a certain point this will be corrected automatically. |
otherError | Surge Protection Device (SPD) tripped. Replace. | No | External SPD Device. | Surge Protection Devices (SPD) needs to be replaced. | |
powerSwitchFailure | Contactor welded | Contactor weld resolved | Yes | Very likely requires a maintenance visit with high priority as it is an indication there might now be a properly disconnected socket when no plug is inserted. | |
connectorLockFailure | Plug locking failed | No | Typically caused by not fully inserted plugs, unplugging and attempting to plug again in most cases resolves the problem. | ||
connectorLockFailure | Type 2 actuator stuck, cannot unlock | Type 2 locking actuator recovered | Yes | A mechanical problem, may require a maintenance visit. An Unlock Connector or Hard Reset triggers another attempt to unlock. | |
connectorLockFailure | Could not detect type 2 locking actuator | Type 2 locking actuator detected | Yes | A mechanical problem, may require a maintenance visit. A Hard Reset triggers another attempt to redetect the actuator type. | |
powerMeterFailure | OCPP meter not communicating | OCPP meter communication recovered | Yes | ||
powerMeterFailure | External meter not communicating | External meter communication recovered | No | ||
readerFailure | RFID reader not communicating | RFID reader recovered | No | ||
highTemperature | Can not read temperature sensor | Temp sensor recovered | No | ||
highTemperature | Can not read critical temperature sensor | Critical temp sensor recovered | Yes | ||
otherError | Can not read HMI180 temperature sensor | HMI180 temp sensor recovered | No | ||
otherError | Can not read HMI180 humidity sensor | HMI180 humidity sensor recovered | No | ||
otherError | Voltage drop on HMICP detected | Voltage drop on HMICP recovered | No | ||
otherError | Light sensor on HMICP failure | Light sensor on HMICP failure | No | ||
otherError | Temperature sensor on HMICP failure | Temperature sensor on HMICP failure | No | ||
otherError | Humidity sensor on HMICP failure | Humidity sensor on HMICP failure | No | ||
otherError | Gyroscope sensor on HMICP failure | Gyroscope sensor on HMICP failure | No | ||
otherError | Shock sensor on HMICP failure | Shock sensor on HMICP failure | No | ||
otherError | Communication with HMICP failed | Communication with HMICP failed | No | ||
highTemperature | Housing temperature too high - charging paused | Housing temperature below critical - charging resumed | No | ||
noError | Housing temperature approaching limit - charging current reduced | Housing temperature back to normal - full charging current restored | No | ||
highTemperature | DC wallbox temperature too high - charging paused | DC wallbox temperature below critical | No | ||
highTemperature | Relay temperature too high - charging paused | Relay temperature below critical - charging resumed | No | ||
noError | Relay temperature approaching limit - charging current reduced | Relay temperature back to normal - full charging current restored | No | ||
otherError | Temperature reaches safety limit - emergency stop | Temperature below safety limit - resume | Yes | ||
weakSignal | SignalWeak:0//Not Availa/0 | SignalGood:0//Not Availa/0 | No | Low RSSI limit is 12 and high limit is 14. | |
otherError | GSM SIM card is missing | GSM SIM card inserted | No | GSM SIM card is missing. | Insert a SIM card in the dedicated slot. |
otherError | FW Update in progress | FW Update finished | Yes | FW update command issued while update is already in progress. | Try again after first command was processed. Otherwise carry out a hard reset. |
otherError | No | Firmware update failed. | Try again. | ||
noError | USB communication errors. | USB communication working properly. | No | USB communication errors. | Wait until application recovers from this error. |
otherError | The ChargePoint is tilted. | The ChargePoint no longer is tilted. | Yes | The ChargePoint has been tilted. | A physical inspection and maintenance is required at the ChargePoint location. |
otherError | Possible CP and PR wiring issue. | Possible CP and PR wiring issue is solved. | Yes | A car is detected but no cable is detected. | Check the wiring of CP and PR cables, they may be swapped or the plug may be broken. |
otherError | PR disconnected while car is connected. | PR disconnection issue is solved. | No | The proximity cable is disconnected while the car is plugged | Check the plug and socket PR contact, it may be defect. Check the internal PR wiring of the charging station and the charging cable. |
otherError | OCPP Master and Slave have different SW version. | OCPP Master and Slave have same SW version. | No | The master and slave have different SW versions. | Maybe the firmware update has failed or a manual update was performed incorrectly.Check what is the expected FW version and update firmware. |
otherError | RCMB ext oscillator error. | No | The controller on the ChargePoint has a defect. | Replace the controller on the ChargePoint. | |
otherError | RCMB measurement out of range. | Yes | The current transformer on the Chargepoint has a defect, if this condition persists. | Replace the current transformer on the ChargePoint. | |
otherError | Car current is SOCKET_TYPE2_CURR_OVERLOAD_THRESHOLD_1% more than expected. | Car is charging at nominal current. | No | The car is charging with SOCKET_TYPE2_CURR_OVERLOAD_THRESHOLD_1% more than expected according to the signaled current. The charge point will try to solve it by decreasing the signaled current | Check the car. |
otherError | Car current overload, charging stopped. | Car is charging at nominal current again. | Yes | The car is charging with a too high current. Charging will be stopped | Check the car. |
connectorLockFailure | Actuator unlocked while charging | Yes | For some reason the actuator was unplugged during charging. | Verify the actuator and actuator wiring | |
otherError | Not all DLM Slaves connected | All DLM Slaves are connected again | No | Some DLM slaves are disconnected from DLM master. | Reconnect the DLM slaves to the DLM master again. |
otherError | DLM Slave disconnected and not charging | DLM Slave is connected again | No | The DLM slave is disconnected from DLM master and its DisconnectedLimit is set to zero. | Reconnect the DLM slave to the DLM master again or increase its DisconnectedLimit. |
otherError | USB stick handling finished | Yes | USB stick is inserted and is being handled. | Wait until all operations are finished. | |
otherError | Phase rotation failure. | Phase rotation direction normal. | Yes | A different phase rotation dir. has been detected from the option selected in the configuration. Phases have either been incorrectly installed, or misconfigured. | Configuration has to be changed consistently according to detected phase rotation dir., or the phases have to be correctly installed. A physical inspection and maintenance may be required at the chargepoint location. |
underVoltage | There is no power on mains. | Grid power restored. | Yes | No power on mains has been detected. | A physical inspection and maintenance is required at the chargepoint location. |
otherError | Failed init: SSH, timezone, USBLIB | No | A component or set of components failed to initialize correctly. | An inspection and maintenance is required for the chargepoint, issue probably has to be escalated to be handled by a support engineer. | |
otherError | State D detected, charging is paused | Car no longer in state D, charging is resumed | No | Charging is paused because state D is detected. | Check the reason why car goes to state D. |
underVoltage | Low voltage detected, charging is paused | Normal voltage detected, charging is resumed | No | Charging is paused because low voltage is detected. Charging will resume one minute after the electric grid stabilizes | Wait until the electric grid stabilizes. |
overVoltage | High voltage detected, charging is paused | Normal voltage detected, charging is resumed | No | Charging is paused because high voltage is detected. Charging will resume one minute after the electric grid stabilizes | Wait until the electric grid stabilizes. |
otherError | Low frequency detected, charging is paused | Normal frequency detected, charging is resumed | No | Charging is paused because low frequency is detected. Charging will resume one minute after the electric grid stabilizes | Wait until the electric grid stabilizes. |
overCurrentFailure | RCD-MCB triggered from unique input | RCD-MCB from unique input reconnected | Yes | RCD-MCB needs to be re-armed. | |
noError | USB stick handling: Finalized - Please remove USB stick | USB stick handling: Finalized - Please remove USB stick | No | USB stick is still inserted while all previous operations completed successfully. | Remove the USB stick. |
noError | USB stick handling: Finalized with error - Please remove USB stick | USB stick handling: Finalized with error - Please remove USB stick | No | USB stick is still inserted while there were errors with previous operations. | Remove the USB stick and retry. |
noError | Socket type 2 plug lifetime exceeded | No | Socket type 2 plug should be replaced. | ||
connectorLockFailure | Actuator emergency opener faulted | Yes | A mechanical problem, may require a maintenance visit. | ||
groundFailure | Ground check (PE) failed | Ground check (PE) failure solved | No | A wiring problem, may require a maintenance visit. | |
underVoltage | L1 voltage is missing | L1 voltage is not missing (contactor opened) | No | L1 line is not energized when it should since the contactor is closed | Verify that the charger wiring is correctand that no RCD or MCB protection is active. |
underVoltage | No | Error occurs if issued power line is either not connected or the varistor at this line is defective. | Check varistor fault or mains outage. | ||
otherError | Message queue is full | Message queue works again | Yes | Error occurs when the parameter "OcppQueueFullAsErrorState"was set by operator and the OCPP message queue is full and can not store further items. | Check the connection to the OCPP backend. |
otherError | Internal communication error | Internal communication error resolved | Yes | Unexpected internal SW communication error. | A system reboot is required. |
otherError | OCPP meter failure | OCPP meter failure resolved | Yes | OCPP meter reported a failure in the power line supply. | Check the power lines voltage, frequency and current. |
internalError | 15118 module failure | 15118 module failure resolved | No | 15118 module failed to initialize. | Reboot the chargepoint or check for hardware issues. |
internalError | QCA7000 initialization failure | QCA7000 initialization failure resolved | No | QCA7000 initialization failure. | Reboot the chargepoint or check for hardware issues. |
weakSignal | eth interface had 0 link up-down sequences. | Too many eth link up-down sequences resolved | No | Ethernet interface is having frequent disconnection and connections. | Verify the LAN network settings and state. |
noError | Socket type 2 contactor lifetime exceeded | No | Socket type 2 contactor should be replaced. | ||
underVoltage | Contactor not closed | Contactor error solved | No | Contactor or main relay has failed to close or it opened during charging | Verify that the charger wiring is correctand that the relay is in good condition. |
otherError | DLM Slave solar mode is incorrectly configured | DLM Slave solar mode is now correctly configured | No | A DLM Slave has solar mode enabled but the DLM Master it's connected to does not support it. | Verify that the slave DLM parameters are configured consistently with the DLM master parameters. |
otherError | CP ADC calibration aborted. (Value out of range) | No | CP ADC calibration was aborted due to an out of range ADC value. | The board might need an inspection by a technician. | |
otherError | WLAN SSID or PSK is incorrectly configured | WLAN SSID and PSK are now correctly configured | No | WLAN was enabled but the SSID or the PSK was wrong. | Verify that WLAN SSID and the PSK was set correctly. |
otherError | Fan defect, ventilation could not be started | Fan ventilation functionality recovered | Yes | ||
otherError | Shock detected | Shock is not longer detected | Yes | ||
otherError | Tilt detected | Tilt is not longer detected | Yes | ||
otherError | Humidity is too high | Humidity is back to normal | No | ||
otherError | HMI180 temperature too low | HMI180 temperature back to normal | No | ||
otherError | HMI180 USB error | HMI180 USB error solved | No | ||
otherError | HMI180 USB communication error | HMI180 USB communication error solved | Yes | ||
otherError | Phytec temperature too high | Phytec temperature back to normal | Yes | ||
otherError | Phytec LCD temperature too high | Phytec LCD temperature back to normal | Yes | ||
otherError | Phytec LCD temperature too low | Phytec LCD temperature back to normal | No | ||
otherError | HMI180 Phytec communication error | HMI180 Phytec communication error solved | No | ||
otherError | LED ring temperature too high | LED ring temperature back to normal | No | ||
otherError | LED ring temperature too low | LED ring temperature back to normal | No | ||
otherError | LED group failure | LED group failure solved | No | ||
otherError | Payter temperature too high | Payter temperature back to normal | No | ||
otherError | Payter temperature too low | Payter temperature back to normal | No | ||
otherError | Payter communication error | Payter communication error solved | No | ||
otherError | WIFI module communication error | WIFI module communication error solved | No | ||
otherError | WIFI temperature too high | WIFI temperature back to normal | No | ||
noError | Defined number of cycles for under load has been reached | No | Socket type 2 contactor should be replaced. | ||
noError | Authorization failed. | No | |||
otherError | Firmware update failed. | No | Firmware update failed (internet connection?). | Retry or perform a manual update. | |
resetFailure | Unintended Reset - Power Outage? | No | |||
resetFailure | Terminated transaction after reset! Power Outage? | No | ChargePoint rebooted while a transaction (charging) was active. Transaction was implicitely terminated. | Restart the transaction. | |
otherError | Slave is unavailable (disconnected from Master). | No | A Slave disconnected from the master. | Replace cable, repair connection, and wait until slave reconnects to master. | |
otherError | Diagnostics failed. | No | Diagnostics failed (internet connection?). | Retry. | |
groundFailure | RCMB error. | No | |||
evCommunicationError | 15118 communication error (exi decoder) | No | 15118 communication failed | ||
evCommunicationError | 15118 communication error (exi encoder) | No | 15118 communication failed | ||
evCommunicationError | 15118 communication error (TLS cert) | No | 15118 communication failed | ||
evCommunicationError | 15118 communication error (V2G session id) | No | 15118 communication failed | ||
evCommunicationError | 15118 communication error (TCP) | No | 15118 communication failed | ||
otherError | 15118 authorization failed | No | 15118 authorization for PnC failed. The signature validation failed | Install a valid certificate in the car and the correct root CA in the chargepoint | |
otherError | 15118 authentication failed | No | 15118 authentication for PnC failed | Install a valid certificate in the car and the correct root CA in the chargepoint | |
otherError | 15118 certificate installation failed | No | 15118 Certificate Installation failed | Verify that car and backend are handling the certificates properly | |
noError | System not yet ready. | No |